CVE-2018-7522: Supervisor-level privilege escalation in Schneider Electric Triconex Tricon MP 3008
- Vendor
- Schneider Electric
CVE-2018-7522 affects Schneider Electric Triconex Tricon MP Model 3008 firmware versions 10.0–10.4. During a system call, processor registers are saved to a fixed memory location. An attacker who modifies the saved register data could gain supervisor-level access and control system states. HatMan malware targeted this vulnerability together with CVE-2018-8872 to install additional functionality in controller firmware.
Impact, mitigation & remediation
What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.
Impact
What an attacker gets, and what they’ve been doing with it.
Exploitation could elevate an attacker to supervisor-level access and enable unauthorized control of controller system states. The combined advisory for CVE-2018-7522 and CVE-2018-8872 identifies possible arbitrary code execution, system shutdown, and compromised safety functions; it does not distinguish which of these broader outcomes follows from each vulnerability independently.
Mitigation
If you can’t patch tonight, do this now.
Isolate safety-system networks behind firewalls, prevent Internet exposure, and restrict remote access. Enable Triconex cybersecurity features, restrict physical access, and place controllers in locked cabinets. Do not leave controllers in PROGRAM mode, and configure operator stations to alarm when that mode is enabled. Secure TriStation engineering workstations and connect them only to the safety network. Scan removable media and verify that computers are malware-free before connecting them to safety systems. Assess operational and safety risks before deploying defensive changes.
Remediation
Patch, then assume compromise.
Upgrade to the latest supported Triconex Tricon CX version with Schneider Electric assistance. Tricon CX v11.4 was identified as available with security enhancements addressing HatMan techniques and other sophisticated attacks. For suspected compromise, engage Schneider Electric to collect and analyze installation data and perform necessary malware removal procedures.
Exploits
No public exploits tracked yet. Mallory keeps watching.
Affected products & vendors
Products and vendors Mallory has correlated with this vulnerability. Open in Mallory to drill down to specific CPE configurations and version ranges.
References
Frequently asked questions
- Is CVE-2018-7522 exploited in the wild?
- As of Oct 16, 2026, Mallory has no reports of CVE-2018-7522 being exploited in the wild. It is not listed in CISA KEV.
- Is there a public exploit for CVE-2018-7522?
- As of Oct 16, 2026, Mallory has found no public exploit for CVE-2018-7522.
- Is there a patch for CVE-2018-7522?
- Upgrade to the latest supported Triconex Tricon CX version with Schneider Electric assistance. Tricon CX v11.4 was identified as available with security enhancements addressing HatMan techniques and other sophisticated attacks.
- What products are affected by CVE-2018-7522?
- Schneider Electric Triconex Tricon Mp 3008 Firmware.
- How severe is CVE-2018-7522?
- CVE-2018-7522 has a CVSS v3 score of 6.7 (Medium) and an EPSS score of 0.42% (28th percentile) as of Oct 16, 2026.
Recent activity
3 sources tracked across advisories, community write-ups, and news. New activity surfaces here as Mallory finds it.