CVE-2026-11317: Denial of Service via Crafted CIP Message in Rockwell Automation Logix 5370 and 5570 Controllers
CVE-2026-11317 is a denial-of-service vulnerability affecting Rockwell Automation Logix 5370 and 5570 controllers. According to the provided advisory content, the issue is triggered when an attacker sends a crafted Common Industrial Protocol (CIP) message to an affected device. The fault condition is more likely to impact devices with less memory. Successful exploitation can drive the controller into a major nonrecoverable fault (MNRF), indicating a severe fault state from which normal operation does not automatically resume. The vulnerability is associated with CWE-404.
Impact, mitigation & remediation
What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.
Impact
What an attacker gets, and what they’ve been doing with it.
Successful exploitation can cause a denial-of-service condition on the affected controller, resulting in a major nonrecoverable fault (MNRF). In this state, the device may cease normal operation and require a program download to recover, creating operational disruption and potential process downtime in industrial environments. The provided content indicates availability impact only, with no stated confidentiality or integrity impact.
Mitigation
If you can’t patch tonight, do this now.
CISA-recommended mitigations in the provided content include minimizing network exposure for control system devices, ensuring affected systems are not directly accessible from the internet, placing control system networks and remote devices behind firewalls and isolating them from business networks, and using secure remote-access methods such as VPNs while keeping those solutions updated. These measures reduce the likelihood that an attacker can deliver the crafted CIP message required for exploitation.
Remediation
Patch, then assume compromise.
Apply the vendor-provided fix or update referenced in Rockwell Automation Security Advisory SD1772 for affected products and versions. The provided content identifies affected versions as CompactLogix 5370 <= 34.016, Compact GuardLogix 5370 <= 35.015, ControlLogix 5570 <= 35.015, and GuardLogix 5570 36.012. If exploitation has already occurred and the device enters an MNRF state, recovery requires a program download.
Exploits
No public exploits tracked yet. Mallory keeps watching.
Frequently asked questions
- Is CVE-2026-11317 exploited in the wild?
- As of Sep 25, 2026, Mallory has no reports of CVE-2026-11317 being exploited in the wild. It is not listed in CISA KEV.
- Is there a public exploit for CVE-2026-11317?
- As of Sep 25, 2026, Mallory has found no public exploit for CVE-2026-11317.
- Is there a patch for CVE-2026-11317?
- Apply the vendor-provided fix or update referenced in Rockwell Automation Security Advisory SD1772 for affected products and versions. The provided content identifies affected versions as CompactLogix 5370 <= 34.016, Compact GuardLogix 5370 <= 35.015, ControlLogix 5570 <= 35.015, and GuardLogix 5570 36.012.
- How severe is CVE-2026-11317?
- CVE-2026-11317 has a CVSS v4 score of 8.7 (High) and an EPSS score of 0.43% (29th percentile) as of Sep 25, 2026.
Recent activity
8 sources tracked across advisories, community write-ups, and news. New activity surfaces here as Mallory finds it.