CVE-2026-25085: Authentication Bypass in Copeland XWEB Pro

Published Feb 27, 2026 · Updated 4 days ago
Trending this weekNot trendingOutside this week’s top 100
Mention activity · 30 days8 mentions · peak 3 in a dayToday
CVSS9.8Critical · v3.1
EPSS0.76%56th percentile
CISA KEVNoNot listed
In the wildReported2 exploitation records in Mallory
Vendor
Copeland
IdentifiersCVE-2026-25085CWE-394 · Unexpected Status Code or Return…

CVE-2026-25085 is an authentication bypass vulnerability affecting Copeland XWEB Pro firmware version 1.12.1 and earlier, including XWEB 300D PRO, XWEB 500D PRO, and XWEB 500B PRO controllers. In the Lua middleware, an unrecognized authentication mode causes the user_authenticate function to return a table with nil-valued user, role, and recovery fields instead of explicitly rejecting authentication. Because Lua treats tables as truthy and the routing logic checks only for the existence of an authentication object, this result is accepted as legitimate. A manipulated HTTP Authorization header can therefore allow an unauthenticated network attacker to access protected administrative API functions.

Do you run this?See affected versions in your environment and whether adversaries are exploiting this vulnerability against assets like yours.
Check your exposure
Analyst brief

Impact, mitigation & remediation

What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.

Impact

What an attacker gets, and what they’ve been doing with it.

Successful exploitation exposes restricted administrative functions without valid credentials, compromising the confidentiality and integrity of controller management information and potentially disrupting operations. Unauthorized access to refrigeration management functions can enable operational-setting changes with physical consequences. The bypass can also be chained with separate authenticated command-injection vulnerabilities to obtain root-level code execution; root execution is not a direct consequence of this vulnerability alone.

Mitigation

If you can’t patch tonight, do this now.

Remove direct internet exposure of XWEB Pro management interfaces. Place controllers behind firewalls on segmented OT networks isolated from business networks, and restrict management access to authorized systems through a secured, updated VPN or protected management network. Use source-address allowlisting only as a temporary exposure-reduction measure. Monitor administrative access and unexpected changes to controller settings.

Remediation

Patch, then assume compromise.

Upgrade affected Copeland XWEB Pro controllers to firmware version 1.13 or a later vendor-supported release that includes the fix. Confirm the appropriate firmware package for the specific controller model and verify the installed version after updating.

Public exploits

Exploits

No public exploits tracked yet. Mallory keeps watching.

View more in app →
No public exploit code observed for this vulnerability. Mallory keeps watching.
Exposure surface

Affected products & vendors

Products and vendors Mallory has correlated with this vulnerability. Open in Mallory to drill down to specific CPE configurations and version ranges.

VendorProductType
CopelandXweb 300d Pro Firmwareoperating_system
CopelandXweb 500b Pro Firmwareoperating_system
CopelandXweb 500d Pro Firmwareoperating_system
FAQ

Frequently asked questions

Is CVE-2026-25085 exploited in the wild?
Yes. As of Nov 14, 2026, Mallory has reports of exploitation in the wild.
Is there a public exploit for CVE-2026-25085?
As of Nov 14, 2026, Mallory has found no public exploit for CVE-2026-25085.
Is there a patch for CVE-2026-25085?
Upgrade affected Copeland XWEB Pro controllers to firmware version 1.13 or a later vendor-supported release that includes the fix. Confirm the appropriate firmware package for the specific controller model and verify the installed version after updating.
What products are affected by CVE-2026-25085?
Copeland Xweb 300d Pro Firmware, Copeland Xweb 500b Pro Firmware, and Copeland Xweb 500d Pro Firmware.
How severe is CVE-2026-25085?
CVE-2026-25085 has a CVSS v3.1 score of 9.8 (Critical) and an EPSS score of 0.76% (56th percentile) as of Nov 14, 2026.
Activity feed

Recent activity

17 sources tracked across advisories, community write-ups, and news. New activity surfaces here as Mallory finds it.

View more in app →
sh3llc0d3 blogNews · Nov 14, 2026VulnCheck Discloses 14 Unpatched Copeland XWEB | ShellcodeA vulnerability affecting Copeland XWEB Pro versions 1.12.1 and earlier, mentioned as background alongside the primary XWEB EVO disclosures. The article provides no technical description but recommends firmware updates and restricted management access.Read more ↗cyberveilleNews · Nov 9, 2026Botnet de réfrigérateurs : des contrôleurs XWEB PRO détournés en infrastructure SMTP malveillante | CyberVeilleA pre-authentication bypass vulnerability affecting Dixell/Copeland XWEB PRO refrigeration-controller firmware. The content identifies it as exploited in activity abusing internet-exposed controllers as outbound spam/proxy infrastructure. Six confirmed XWEB controllers reportedly exposed vulnerable firmware. Potential refrigeration-temperature manipulation is also highlighted, but researchers have not established a connection between this activity and recent European refrigeration attacks. The investigation is ongoing, and the associated indicators are described as low-to-medium confidence.Read more ↗help net securityNews · Nov 9, 2026Hackers abuse refrigeration controllers to send spam and route proxy traffic - Help Net SecurityAn authentication-bypass vulnerability affecting Copeland XWEB PRO refrigeration controllers, originally made by Dixell. SecurityScorecard suspects attackers exploited it to compromise internet-exposed controllers subsequently abused for coordinated outgoing email, tunneling, and proxy services. The exploitation route is not confirmed; the investigation's overall confidence is low to medium. Separate refrigeration sabotage incidents were not linked to this vulnerability, and one investigated incident involved default administrator credentials rather than vulnerability exploitation.Read more ↗hawkeye blogNews · Nov 6, 2026Weekly Threat Landscape Digest - Week 45 - HawkEyeA Copeland refrigeration-controller vulnerability affecting the listed XWEB PRO models on firmware 1.12.1 or earlier. It appears in an attack report, but its mechanism, individual exploitation status, and patch availability are not specified.Read more ↗
+7 more in the timeline. Sign up to see them
Do you run this?See affected versions in your environment and whether adversaries are exploiting this vulnerability against assets like yours.
Check your exposure
Mallory platform

The version that knows your environment.

This page is what’s public. Mallory adds the parts that aren’t: which of your assets are affected, which adversaries are exploiting it right now, and which detections to deploy tonight.
Exposure mappingQuery your assets running an affected version, and investigate the blast radius.
Threat actor evidenceEvery report linking this CVE to a named adversary.
Associated malwareMalware families linked to this CVE, with evidence and IOCs.
Detection signaturesYARA, Sigma, Snort, and vendor rules, auto-deployed to your SIEM.
Vendor-by-vendor mappingCross-references every affected SKU, including bundled OEM variants.
Social activity5Community discussion across Reddit, Mastodon, and other social sources.