Skip to main content
Mallory
CriticalVulnerability

CVE-2026-3611: Missing Authentication in Honeywell IQ4x Web HMI Default Configuration

Published Mar 12, 2026 · Updated 2 months ago
Trending this weekNot trendingOutside this week’s top 100
Mention activity · 30 daysNo mention activity in the last 30 days.
CVSS10.0Critical · v4
EPSS6.3%94th percentile
CISA KEVNoNot listed
In the wildNoneNo exploitation reported
Vendor
Honeywell
IdentifiersCVE-2026-3611CWE-306 · Missing Authentication for…

CVE-2026-3611 affects Honeywell IQ4x building management controllers in their factory-default configuration. When no web user module has been configured, the controller exposes its full web-based HMI over HTTP without authentication by design. In this state, the device operates under a System Guest (level 100) context that still provides read/write privileges to any remote party able to reach the interface. Authentication is only enforced after a web user is created through U.htm, which dynamically enables the user module. Because U.htm itself is reachable before authentication is enabled, an unauthenticated remote attacker can create a new administrative read/write account, thereby enabling authentication under attacker-controlled credentials. This is a missing-authentication flaw affecting critical management functionality and can result in unauthorized access to controller settings and administrative takeover of the web management plane. Affected firmware spans versions >= 3.50_3.44 and < 4.36_build_4.3.7.9 across multiple Honeywell IQ4x models, including IQ4E, IQ412, IQ422, IQ4NC, IQ41x, IQ3, and IQECO.

Do you run this?See affected versions in your environment and whether adversaries are exploiting this vulnerability against assets like yours.
Check your exposure
Analyst brief

Impact, mitigation & remediation

What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.

Impact

What an attacker gets, and what they’ve been doing with it.

Successful exploitation allows an unauthenticated remote attacker to access the controller’s web HMI with read/write privileges, modify management settings, control connected building-management components, disclose sensitive operational information, and cause denial of service. Because the attacker can create an administrative account before authentication is enabled, they can effectively take over the management interface and lock legitimate operators out of both local and web-based configuration and administration. The provided CVSS v3.1 vector (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H) indicates high impact to confidentiality, integrity, and availability.

Mitigation

If you can’t patch tonight, do this now.

Until patched, restrict network reachability to the controller HTTP interface. Do not expose affected devices directly to the internet. Place control-system networks behind firewalls, isolate them from business networks, and limit access to trusted administrative hosts only. Use secure remote access methods such as VPNs if remote administration is required, and keep those solutions fully updated. As an operational mitigation, immediately configure authorized web-user accounts on devices still in factory-default state so the user module is enabled under legitimate control, reducing the unauthenticated exposure window.

Remediation

Patch, then assume compromise.

Upgrade affected Honeywell IQ4x controllers to a fixed firmware version outside the vulnerable range. The vulnerable range provided is >= 3.50_3.44 and < 4.36_build_4.3.7.9, so remediation requires moving to 4.36_build_4.3.7.9 or later, where available from Honeywell. In addition, ensure a legitimate web user is configured as part of commissioning so that authentication is enabled intentionally under defender-controlled credentials rather than remaining in the insecure default state.

Public exploits

Exploits

No validated public exploits yet. Hidden: 1 rejected by Mallory's analysis as not a working exploit.

View more in app →
Every candidate exploit was rejected by Mallory's analysis.
Exposure surface

Affected products & vendors

Products and vendors Mallory has correlated with this vulnerability. Open in Mallory to drill down to specific CPE configurations and version ranges.

VendorProductType
HoneywellIq412 Firmwareoperating_system
HoneywellIq41X Firmwareoperating_system
HoneywellIq422 Firmwareoperating_system
HoneywellIq4E Firmwareoperating_system
HoneywellIq4Nc Firmwareoperating_system
FAQ

Frequently asked questions

Is CVE-2026-3611 exploited in the wild?
As of Sep 25, 2026, Mallory has no reports of CVE-2026-3611 being exploited in the wild. It is not listed in CISA KEV.
Is there a public exploit for CVE-2026-3611?
As of Sep 25, 2026, Mallory has found no public exploit for CVE-2026-3611.
Is there a patch for CVE-2026-3611?
Upgrade affected Honeywell IQ4x controllers to a fixed firmware version outside the vulnerable range. The vulnerable range provided is >= 3.50_3.44 and < 4.36_build_4.3.7.9, so remediation requires moving to 4.36_build_4.3.7.9 or later, where available from Honeywell.
What products are affected by CVE-2026-3611?
Honeywell Iq412 Firmware, Honeywell Iq41X Firmware, Honeywell Iq422 Firmware, Honeywell Iq4E Firmware, and Honeywell Iq4Nc Firmware.
How severe is CVE-2026-3611?
CVE-2026-3611 has a CVSS v4 score of 10.0 (Critical) and an EPSS score of 6.3% (94th percentile) as of Sep 25, 2026.
Activity feed

Recent activity

10 sources tracked across advisories and community write-ups. News coverage will land here when it surfaces.

View more in app →

No news coverage yet. Advisories and community discussion only.

Do you run this?See affected versions in your environment and whether adversaries are exploiting this vulnerability against assets like yours.
Check your exposure
Mallory platform

The version that knows your environment.

This page is what’s public. Mallory adds the parts that aren’t: which of your assets are affected, which adversaries are exploiting it right now, and which detections to deploy tonight.
Exposure mappingQuery your assets running an affected version, and investigate the blast radius.
Threat actor evidenceEvery report linking this CVE to a named adversary.
Associated malwareMalware families linked to this CVE, with evidence and IOCs.
Detection signaturesYARA, Sigma, Snort, and vendor rules, auto-deployed to your SIEM.
Vendor-by-vendor mappingCross-references every affected SKU, including bundled OEM variants.
Social activity9Community discussion across Reddit, Mastodon, and other social sources.