CVE-2026-58115: Unauthenticated Remote Code Execution in Siemens SIMATIC IoT2050 Node-RED
CVE-2026-58115 is a missing-authentication vulnerability in the Node-RED HTTP administration interface on Siemens SIMATIC IoT2050 Advanced, Basic, M.2, and SM devices. Affected configurations include Industrial OS versions earlier than V4.3.4-1 with Node-RED installed and all Example Image versions with Node-RED installed. The interface permits unauthenticated access to programming functions, allowing remote attackers to deploy malicious flows that invoke system-command execution nodes. Automatically triggered flows can execute arbitrary code with maximum privileges without user interaction. Exploitation has been observed against exposed Node-RED instances, including deployment of command-execution backdoors and attempts to install Linux malware.
Impact, mitigation & remediation
What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.
Impact
What an attacker gets, and what they’ve been doing with it.
Successful exploitation permits complete compromise of the underlying server's confidentiality, integrity, and availability through arbitrary code execution with maximum privileges. Attackers can modify application flows, install malware, establish persistent command-execution backdoors, access locally available data and credentials, and disrupt services. Where the gateway connects enterprise and industrial networks, compromise may also facilitate lateral movement and access to connected OT systems, subject to network reachability and available credentials.
Mitigation
If you can’t patch tonight, do this now.
Uninstall Node-RED if it is unnecessary. Otherwise, enable administrative authentication through adminAuth to protect the editor and administration API, following the Node-RED hardening guidance. Enable HTTPS and separately protect HTTP nodes and dashboards with authentication. Restrict interface access to authorized management systems through network segmentation, firewall rules, and authenticated remote-access controls; do not expose the editor directly to the public internet. Monitor for unexpected flow deployments, execution nodes, HTTP endpoints, and system commands launched by Node-RED.
Remediation
Patch, then assume compromise.
Upgrade affected Industrial OS deployments to the Siemens fixed release V4.3.4-1 or later, also written V4.3.4.1 in associated advisories, following the applicable product-specific instructions in Siemens advisory SSA-834709. No fixed Example Image release is identified in the available information; apply the recommended mitigations to those deployments. Investigate previously exposed systems for unauthorized flows, command-execution HTTP endpoints, suspicious child processes, file modifications, and outbound connections. Remove malicious flows and other persistence mechanisms; updating alone does not eliminate existing compromise.
Exploits
1 exploit validated by Mallory's analysis. Hidden: 1 rejected by Mallory's analysis as not a working exploit.
Frequently asked questions
- Is CVE-2026-58115 exploited in the wild?
- Yes. As of Nov 20, 2026, Mallory has reports of exploitation in the wild.
- Is there a public exploit for CVE-2026-58115?
- Yes. Mallory tracks 1 public exploit or proof of concept for CVE-2026-58115, the earliest disclosed Nov 4, 2026.
- Is there a patch for CVE-2026-58115?
- Upgrade affected Industrial OS deployments to the Siemens fixed release V4.3.4-1 or later, also written V4.3.4.1 in associated advisories, following the applicable product-specific instructions in Siemens advisory SSA-834709. No fixed Example Image release is identified in the available information; apply the recommended mitigations to those deployments.
- How severe is CVE-2026-58115?
- CVE-2026-58115 has a CVSS v4 score of 10.0 (Critical) and an EPSS score of 2.2% (83rd percentile) as of Nov 20, 2026.
Recent activity
127 sources tracked across advisories, community write-ups, and news. New activity surfaces here as Mallory finds it.