Honeywell IQ4x BMS Controller Factory-Default Missing Authentication (CVE-2026-3611)
Attack Surface Exposure · 2 sources · Updated 5mo ago · First seen Mar 12, 2026

Honeywell IQ4x building management system (BMS) controllers were reported to expose their full web-based HMI without authentication in factory-default configurations, tracked as CVE-2026-3611. When no web user module is configured, the device operates under a System Guest (level 100) context that can provide read/write access to anyone who can reach the HTTP interface; authentication is only enforced after a user is created. Because the user-creation function (via U.htm) is reachable prior to authentication, a remote attacker can create an administrative account, enable the user module under attacker-controlled credentials, and potentially lock out legitimate operators, with impacts including unauthorized access to management settings, component control, information disclosure, and denial of service.
This is not fluff; it is a concrete ICS/OT vulnerability disclosure with clear exploitation conditions and operational impact. However, several other items in the set are separate CISA ICS advisories for different products and CVEs (Inductive Automation Ignition deserialization leading to code execution; Apeman camera issues enabling device takeover/viewing feeds; and multiple Lantronix EDS vulnerabilities including auth bypass and root-level command injection) and should be treated as distinct security stories rather than part of the Honeywell IQ4x event.