Six Pre-Authentication RCE Flaws Expose Danfoss Refrigeration Controllers to Takeover
Vulnerability Disclosure · 13 sources · Updated 6h ago · First seen Oct 31, 2023

Midnight Blue researchers reported six previously undisclosed pre-authentication remote code execution vulnerabilities in Danfoss AK-SM800A refrigeration controllers after approximately one hour of manual analysis of firmware 5.3.2. They demonstrated root-level execution on firmware 3.3.0 and said the underlying flaws remain in 5.3.2. Strict session control blocks unauthenticated access to many vulnerable handlers, but its authentication gateway also contains a memory-corruption flaw that researchers say could be developed into pre-authentication RCE. The investigation followed attack waves against refrigeration controllers beginning in France on October 11 and recurring on November 2; the report does not establish that these newly discovered flaws were exploited in those attacks.
Missing exploit mitigations and disabled secure boot increase the potential for persistent compromise, repeated refrigeration disruption and destructive attacks. Coordinated disclosure with Danfoss is ongoing, and researchers prioritize removing public management access through VPNs, private APNs or tightly restricted firewall allowlists rather than relying solely on patches or strict mode. Separately, a Synacktiv advisory updated in 2023 documented an authentication bypass in Danfoss SM800 and SC255 devices through firmware v08.095.008: attackers with network access could derive a valid daily access code from the device’s unauthenticated date. Danfoss identified those products as end-of-life and recommended restricting network access, reinforcing the need to isolate exposed refrigeration management interfaces.